Applies To: |
|
Summary: |
When Importing or Linking from a Mitsubishi MXChange CDE server, Values 30 and 140 in Mitsubishi's IOtype field were translating to "INTEGER" in Citect's Type field, instead of "INT". This would cause a compile error, and was due to an error in the format file. |
Solution: |
CIT has confirmed this to be a problem in Citect for Windows version 5.20. This problem has been fixed in versions 5.21 and 5.30. |
Keywords: |
Related Links
Attachments