In versions 3.x the [Alarm]SaveStyle
parameter was correctly documented. Values of 1 and 2 can be used
to save the records with record number or alarm tag identifiers,
respectively. These values are still supported in versions 5.x. In
version 5.x new values of 2 and 3 are used for these same alarm
record saving styles. Currently values 1 and 2 are translated to 3
and 4 respectively in Citect. This can allow future flexibility.
Using the version 5.x or 4.x documented values of 0 and 1 will both
result in saving with record number identifier because 0 is not
supported.
CIT has confirmed this to be a problem in Citect for Windows
version 4.x to 5.21. The documentation will be amended for future
versions.
|