Applies To:
  • CitectSCADA 5.20

Summary:
Associating STRING variable to untyped super genie substitution, eg. ?1? causes error dialog to pop up.  The dialog cannot be dismissed.  When changing page while the dialog is up causes GP at Citect runtime.  The Error dialog pops up is as follows:

File (E:\v521\source\display\CT_EXEC.C) Line (2243) Error Invalid Load Variable Type.

 

Solution:
CIT has confirmed this to be a problem in Citect for Windows versions 5.20 to 5.21. This problem has been fixed in version 5.21 Service Pack A. 

Keywords:
 