Applies To:
  • CitectSCADA 5.xx

Summary:
An "Out of memory" Citect compiler error occurs with a context message of "Allocating Wrt Table".  The error happens when compiling a large project for which there were greater than or equal to 32500 event tags, each writing to a different tag address. 

Solution:
CIT has confirmed this to be a problem in Citect for Windows versions 4.xx and 5.xx.  This problem has been fixed in version 5.21 Service Pack B. 

Keywords:
 

Attachments