How to Connect Keyence KZ-A500 Series PLC with KZ-L10 To Citect? |
Solution: |
MELSEC Protocol with Citect driver for
Mitsubishi/Melsec-A Series can be used for KZ-L10 to communicate to
Citect. An example for quick default setup is given as follows.
(1) Follow the guide of Express Communications Wizard, select "Serial via Computer Link Module" under Mitsubishi/Melsec-A Series from Citect Driver List. (2) Set switches on the KZ-L10 accordingly: INTERFACE --P1(232C) TERMINATOR -- OFF STATION No. 0 A1 -- OFF: Normal A2 -- OFF A3 -- ON : Write during RUN enabled A4 -- ON : Sum check set B1 -- OFF: B2 -- OFF B3 -- ON : B4 -- OFF : 7 bits B5 -- OFF: Parity None B6 -- OFF B7 -- OFF : Stop bit 1 B8 -- OFF : C1 -- ON : Protocol Mode1 C2 -- OFF C3 -- OFF : C4 -- OFF : C5 -- ON : C6 -- OFF C7 -- OFF : C8 -- OFF : (3) Wiring detail (a) KZ-L10 PORT1 PC RS-232C COM PORT 25-WAY MALE 9-WAY FEMALE 2 (TX)----------------------- 2( RX) 3 (RX)---------------------- 3( TX) 4 (RTS)-------------------- 8( CTS) 5 (CTS)---------------------7( RTS) 7 (SG) -------------------- 5( SG) |---4(DTR) |---6(DSR) Note: Short Pin 4 and 6 at PC side (b) KZ-L10 PORT1 PC RS-232C COM PORT 25-WAY MALE 25-WAY FEMALE 2 (TX)----------------------- 3( RX) 3 (RX)---------------------- 2( TX) 4 (RTS)-------------------- 5( CTS) 5 (CTS)---------------------4( RTS) 7 (SG) -------------------- 7( SG) |---6(DTR) |--20(DSR) Note: Short Pin 6 and 20 at PC side |