How to Connect Keyence KZ-A500 Series PLC with KZ-L10 To Citect? 

Solution:
MELSEC Protocol with Citect driver for Mitsubishi/Melsec-A Series can be used for KZ-L10 to communicate to Citect. An example for quick default setup is given as follows.

(1) Follow the guide of Express Communications Wizard, select "Serial via Computer Link Module" under Mitsubishi/Melsec-A Series from Citect Driver List.

(2) Set switches on the KZ-L10 accordingly:

INTERFACE --P1(232C)

TERMINATOR -- OFF

STATION No. 0

A1 -- OFF: Normal

A2 -- OFF

A3 -- ON : Write during RUN enabled

A4 -- ON : Sum check set

B1 -- OFF:

B2 -- OFF

B3 -- ON :

B4 -- OFF : 7 bits

B5 -- OFF: Parity None

B6 -- OFF

B7 -- OFF : Stop bit 1

B8 -- OFF :

C1 -- ON : Protocol Mode1

C2 -- OFF

C3 -- OFF :

C4 -- OFF :

C5 -- ON :

C6 -- OFF

C7 -- OFF :

C8 -- OFF :

(3) Wiring detail

(a)

KZ-L10 PORT1 PC RS-232C COM PORT

25-WAY MALE 9-WAY FEMALE

2 (TX)----------------------- 2( RX)

3 (RX)---------------------- 3( TX)

4 (RTS)-------------------- 8( CTS)

5 (CTS)---------------------7( RTS)

7 (SG) -------------------- 5( SG)

|---4(DTR)

|---6(DSR)

Note: Short Pin 4 and 6 at PC side

(b)

KZ-L10 PORT1 PC RS-232C COM PORT

25-WAY MALE 25-WAY FEMALE

2 (TX)----------------------- 3( RX)

3 (RX)---------------------- 2( TX)

4 (RTS)-------------------- 5( CTS)

5 (CTS)---------------------4( RTS)

7 (SG) -------------------- 7( SG)

|---6(DTR)

|--20(DSR)

Note: Short Pin 6 and 20 at PC side

 