Applies To:
  • CitectSCADA 3.xx, 4.xx, 5.xx

Summary:
Windows created by WinNewAt() are displayed incorrectly at (0,0) coordinates when the page size is larger than the screen. This happens regardless of what the value of [Page]DynamicSizing is.

This problem also occurs when the page is smaller than the screen but it is displayed partially or fully off screen when [Page]DynamicSizing = 0.

 

Solution:
Windows created by WinNewAt() are now displayed correctly at the specified coordinates when the page size is larger than the screen.

Moreover, a new parameter called [Page]OutOfScreenAdjustment has been created to enable or disable adjustment whenever the window created is out of screen. Setting the parameter to 0 in Citect.ini will disable the adjustment to 0/0 position.

CIT has confirmed this to be a problem in Citect for Windows versions to 5.21. This problem has been fixed in version 5.21 Service Pack A.

 