Applies To:
  • CitectSCADA 3.xx, 4.xx, 5.xx

File extension "v52" for symbol and genie library files.  When CtDraw32 crashes during a pack libraries it leaves the name of the libraries with an extension "V52" regardless of whether it was a Symbol or Genie that was last worked on in the code that packs the library.  Attempting to repack the libraries again can not differentiate between a symbol and genie library files.

Note: "v52" will be "v51" in Citect version 5.1


Change the temporary files name(*.v52) to *.l52 for symbols library, *.g52 for genie library and remain the same (*.v52) for template library.

CIT has confirmed this to be a problem in Citect for Windows versions 3.XX to 5.21.  This problem has been fixed in version 5.21 Service Pack A.