Applies To:
  • CitectSCADA 5.xx

Summary:
The TrnInfo() function does not correctly return values greater than 32767 when using mode 6.  This causes a problem when using this function and mode when there are more than 32767 events, as the number turns negative. 

Solution:
CIT has confirmed this to be a problem in Citect for Windows versions 5.xx. This problem has been fixed in version 5.21 Service Pack B. 

Keywords:
 

Attachments