Applies To: |
|
Summary: |
Citect crashes when DspAnFree(An) is called on a Cicode object that has something continuously displayed on it. |
Solution: |
CIT has confirmed this to be a problem in Citect for Windows versions 5.20 to 5.21. The Function DspText() displays text on animation point now checks if the Animation point has been freed. This problem has been fixed in version 5.21 Service Pack C. |
Keywords: |
Related Links
Attachments