Applies To:
  • CitectSCADA 5.xx

Summary:
I am getting this hardware alarm; " General Out of memory xxx0000#Error not in database "

Also the #MEM communication failure error displays on the page for some of my variables. The variables are configured using the Alarm properties as tags, such as, Boiler_1.LL or Boiler_1.HH, etc. What can cause this out of memory error?

 

Solution:
Check the project(s) and ensure that an ALARM device has been created for your Alarm Tags. That is, an ALARM I/O device. 

Keywords:
 

Attachments