Applies To: |
|
Summary: |
The MICROD driver is getting a "Response bad or garbled" error, however the device seems to have no communication problems and is returning correct response packets. |
Solution: |
CIT has confirmed this to be a problem in the MICROD driver. It has been found that the MICROD driver is incorrectly calculating the expected response length. This problem has been fixed in MICROD driver version 2.00.03. |
Keywords: |