Applies To: |
|
Summary: |
I want to read some PID block elements from
an Allen Bradley PLC5, but none of the Citect drivers seem to
support the following addresses:
.DFD Bit 5 Derivative Smoothing
Disabled Is there anything I can do? |
Solution: |
The Citect compiler uses the AB5.DBF file
in the \Citect\Bin directory as a template to check for valid
Variable Tag addresses. There are a lot of possible
combinations of PLC5 data types and addresses and not every
possible address that the driver can support has been included in
this template. In this case the AB5.DBF can be edited and the
following 2 lines -
PD%F:%U%*41.%u<PE=0,MO,CA,SWM=4,DO=6,PVT,CL,CT,EN=15,PVHA,PVLA,DVPA> changed to - PD%F:%U%*41.%u<PE=0,MO,CA,SWM=4,DFD,DO,PVT,CL,CT,ZCD,BCD,EN=15> NOTES: If you are using MS Excel for editing, then first open the file: \Citect\Bin\Save_dbf.xls, then open the AB5.DBF file. When you are done, right-click on any cell and choose Save/Close DBF, then quit Excel without saving. CIT does not guarantee that drivers will work with addresses other then standard in the drivers supplied with the release version of Citect. For more information contact Citect Support or see the Citect Driver Development Kit documentation. |
Keywords: |
Related Links
Attachments