Applies To:
  • CitectSCADA 5.xx

Summary:
I can use the CCSARC driver (v2.01.00.000) with the old PCX20 (Rev. B) Arcnet card without any problems, but when I used this driver with the new PCX20 (Rev. D) Arcnet card, Citect will freeze during start-up.  

Solution:
CIT has confirmed this to be a problem in CCSARC driver version v2.01.00.000 and earlier. This problem has been fixed in CCSARC driver version v2.01.01.000. 

Keywords:
 

Attachments