When trying to connect to an existing IO Server, the IO Server crashes with the error message "Req size too big <n>". The IO Server is communicating to a Toshiba device using the TOSADMAP driver. |
Solution: |
We modified the "Protdir.dbf" file on the
client PC. Fields "Bit_Block" and "Max_Length" were both changed
from 1024 to 64.
(See also Q1181) |