Applies To:
  • CitectSCADA 3.xx, 4.xx, 5.xx

A crash in the Citect compiler occurs.  The error happens when compiling a project which includes a large number of group entries.  There is at least one group which encompasses multiple sub-groups, so that the total number of associations for the group is greater than 256. 

CIT has confirmed this to be a problem in Citect for Windows versions 3.xx, 4.xx and 5.xx. The maximum number of associations permitted to be associated with a single group on compilation has been increased from 256 to 16376.  This problem has been fixed in version 5.21 Service Pack D.