The SNMP driver does not initialise if the
wrong version of the file mfc42.dll is present in the system32
folder.
Version 4.2.6068 of mfc42.dll is installed with Windows NT and
is not updated in service packs up to 6a. Installing Citect version
5.21 updates the file to version 4.21.7303. Citect service packs up
to Serv. Pack E do not update the file further. The SNMP driver
will not initialise with these versions of mfc42.dll.
The SNMP driver does function correctly with version 6.00.8447.0
of mfc42.dll. At the time of writing, this file is installed with
Citect version 5.30 Beta1. It is also included in an
installation of Microsoft Visual C 5.0.
|