Applies To:
  • CitectSCADA

When Internet Display Client connects to the internet server, it will ask for [DNS] and [Client] information from the internet server's citect.ini file and then it will put the information to Internet Display Client's citect.ini file.  The problem occurs when the information inside [DNS] or [Client] section exceeds 256 characters.  In this case only the first 256 characters of information are transferred. 

CIT has confirmed this to be a problem in Citect for Windows versions 5.XX. This problem has been fixed in version 5.21 Service Pack E.