Applies To:
  • CitectSCADA

A device will still create a history files even if time and period is not specified.

The following parameter has been added


CreateHistoryFiles = 1 // will work as previously prior to this change, i.e history file will be created.

CreateHistoryFiles = 0 // History file will not be created if time and period is not specified in the device.

The default value will be 1.


CIT has confirmed this to be a problem in Citect for Windows versions 5.20 to 5.21. This problem has been fixed in version 5.21 Service Pack G.