Applies To: |
|
Summary: |
A device will still create a history files
even if time and period is not specified.
The following parameter has been added [Device] CreateHistoryFiles = 1 // will work as previously prior to this change, i.e history file will be created. CreateHistoryFiles = 0 // History file will not be created if time and period is not specified in the device. The default value will be 1. |
Solution: |
CIT has confirmed this to be a problem in Citect for Windows versions 5.20 to 5.21. This problem has been fixed in version 5.21 Service Pack G. |
Keywords: |
Related Links