Applies To:
  • CitectSCADA 5.xx

Summary:
Citect takes a long time to respond (or even bringing the unit offline) after the cable has been disconnected/connected to the Siemens S7 PLCs. This only happens if there is a network of S7 PLCs connected to a single Citect PC.

This situation also happens when Citect starts up and one of the PLCs is offline.

 

Solution:
The function of the standard driver parameter Timeout had been modified so that it no longer controls the timeout duration.

A new parameter has been added to control the timeout duration when the driver does not receive a response from the S7 API. This parameter is designated "ConnTimeout". The default time for timeout is 5000ms.

CIT has confirmed this to be a problem in the S7 drivers up to and including V2.03.00. This has been fixed in version 2.03.01 and upwards.

 