Applies To:
  • CitectSCADA 5.30

Summary:
Citect display the ACKNOWLEDGED alarms in the order they are acknowledged, not in the order of their time of occurrence (ON time). 

Solution:
New parameters added. Two new alarm parameters have been added to control the order in which the alarms appear in the alarm list. The details are as follows:

[Alarm]

Sort=0 (default) Alarms appear in the order they are acknowledged as in previous
Sort=1 Enable sorting of alarms by their ON time
SortMode=0 (default) Descending, which shows the most recent alarm at the top
SortMode=1 Ascending, which shows the oldest alarm at the top

This alarm sorting feature is available in Citect version 5.30 Service Pack A.

 