Applies To:
  • CitectSCADA 4.xx, 5.xx

If I set [Intl]sDecimal=, and [Intl]bDecimal=0, I get a '.' as decimal separator instead of the ',' that I would expect. 

When the [intl]bDecimal is set to 1 or is left blank, Citect will use the Windows default for the Number Format Decimal Separator, regardless of what [intl]sDecimal is set to. When [intl]bDecimal is set to 0, Citect will use the value stored in [intl]sDecimal as the Number Format Decimal Separator.

CIT has confirmed this to be a problem in Citect for Windows versions to 5.21 Service Pack G. This problem has been fixed in version 5.31.