Applies To: |
|
Summary: |
StrToTime will return a valid time even if there is an error in the string eg. "12:aa:00" will return 43200 which is equivalent to "12:00:00". |
Solution: |
CIT has confirmed this to be a problem in Citect for Windows versions to 5.30. This problem has been fixed in version 5.30 Service Pack A. The function now returns -1 if the string is invalid. |
Keywords: |
Related Links