Applies To:
  • CitectSCADA 5.21, 5.30, 5.31

Summary:
If a download of a graphics page fails due to insufficient disk space on an Internet Display Client no subsequent attempts will be made to download the graphics page, even when sufficient disk space becomes available. 

Solution:
To workaround this problem perform the following steps:

1) Free up sufficient disk space.

2) Delete any .ctf, .ctg or .rdb files for the affected graphics page from the project folder.

3) Delete any .ctf, .ctg or .rdb files for the affected graphics page from the operating system's Temporary Internet Files folder.

4) Reselect the graphics page from within Citect.

CIT has confirmed this to be a problem in Citect for Windows versions 5.21 to 5.31. This problem has been fixed in version 5.40.

 

Keywords:
 

Attachments