Applies To:
  • CitectSCADA 5.21

Summary:
If you define an alarm and select "Display the alarm on the Alarm Page" to FALSE then the alarm will NOT show up on the Disabled Alarm Page when the alarm is disabled (using AlarmDisable). 

Solution:
The problem has been augmented so that disabled alarms appear on the disabled alarms page if they are configured to be displayed on the alarms page or the summary page.

CIT has confirmed this to be a problem in Citect for Windows versions 5.21 This problem has been fixed in version 5.30

 

Keywords:
 