Applies To: |
|
Summary: |
This problem only occurs if you shut down before Trend Redundancy requests have stopped and one or more of the [TREND] CachesSize0..8 parameters are set to low values (below 50). Even then it may not occur reliably. The same situation may also cause a 'Pure Virtual Function Call' message box to appear. |
Solution: |
CIT has confirmed this to be a problem in Citect for Windows versions 5.31. This problem has been fixed in version 5.40. |
Keywords: |
Related Links