Applies To: |
|
Summary: |
The SQLGetField() function truncates fields of 'LONG' data types. When using the SQLGetField() function, the values in 'LONG' data type fields are truncated to a string of length 10 if the values are -1,000,000,000 or below. |
Solution: |
CIT has confirmed this to be a problem in Citect for Windows versions up to 5.31. This problem has been fixed in version 5.40. |