Applies To:
  • CitectSCADA 5.20

Summary:
Error in the comli.dbf (In Version 5.20):

    A%O%/4 0 1 16 0 0o3770 Analog

According to the comli standard it should be:

    A%O%/4 0 1 16 0 0o37777 Analog

 

Solution:
CIT has confirmed this to be a problem in Citect for Windows versions 3.XX to 5.21. This problem has been fixed in version 5.21 Service Pack B. 

Keywords:
 

Attachments