Genie substitutions do not work anymore if
you associate any of the following names in the genie substitution
field.
{"TEXT", "FONT", "VISIBLE", "MVX", "MVY", "ROT", "SZX", "SZY", "FIL", "CMD", "DOWN_CMD", "DBLCLK_CMD", "REPEAT_CMD", "MSG_LOG", "MVXSL", "MVYSL", "ROTSL", "PRIV", "AREA", "DEVICE", "DESC", "COMMENT", "DISABLED", "SET_ARR"} The problem is case sensitive For Example. - Create a Genie. - Enter the following Substitution expression . %AREA% |
Solution: |
CIT has confirmed this to be a problem in Citect for Windows versions 5.21 to Service Pack E. This problem has been fixed in version 5.21 service Pack F. |