Applies To:
  • CitectSCADA 5.xx

The Citect compiler may incorrectly compile RTF report format files created by some word processors. Some tag variables may be printed incorrectly or not at all. The report format files created by Microsoft WordPad in Windows 98 and Windows 2000 are known to cause this problem. 

Until the problem is corrected avoid using Microsoft WordPad for creating RTF report format files.

CIT has confirmed this to be a problem in Citect for Windows versions 5.XX. This problem has been fixed in version 5.40