Applies To:
  • CitectSCADA 5.xx

Summary:
When the Yokgrn driver is used in Citect to connect to multiple Yokogawa devices on separate ports, Citect will often display the data incorrectly. Citect displays the data from one I/O device for another I/O device.  

Solution:
CIT has confirmed this to be a problem in the Yokgrn driver for versions up to and including V2.01.00.242. This problem has been fixed in driver version V2.01.01.00 and above. 

Keywords:
 

Attachments