Applies To:
  • CitectSCADA 3.xx, 4.xx, 5.xx

When I try to start Graphics Builder or Project Editor from the menu on the application control menu of the running Citect32, I get error messages and the apps do not start. Starting these apps is OK when they are already running and starting Citect Explorer is OK. We would like to get rid of the error messages with the least effort:  

You can set the [Win]configure=0 parameter to disable this from the control menu. You can do this from the Citect Help or directly by editing your Citect.ini file.