Applies To: |
|
Summary: |
I am using the latest Kingfish driver (V1.00.00.000 ) to connect Citect to the Kingfisher RTU via TCP/IP. After Citect has finished starting up and reports all all I/O devices as "ONLINE", I then disconnect and re-connect the ethernet cable. Citect then fails to bring the all I/O devices online again. |
Solution: |
The driver code has been modified so that
if the Kingfisher RTU does not respond after the TimeOuts and
Retries, the communication channel is considered offline. This will
put all I/O devices defined for that channel to be also considered
offline and will be restarted.
This problem has been fixed in driver version V1.00.01.00 and above. |
Keywords: |
Related Links
Attachments