Applies To:
  • CitectSCADA

Summary:
I am using the latest Kingfish driver (V1.00.00.000 ) to connect Citect to the Kingfisher RTU via TCP/IP. After Citect has finished starting up and reports all all I/O devices as "ONLINE", I then disconnect and re-connect the ethernet cable. Citect then fails to bring the all I/O devices online again. 

Solution:
The driver code has been modified so that if the Kingfisher RTU does not respond after the TimeOuts and Retries, the communication channel is considered offline. This will put all I/O devices defined for that channel to be also considered offline and will be restarted.

This problem has been fixed in driver version V1.00.01.00 and above.

 