  • CitectSCADA

I am using the latest Kingfish driver (V1.00.00.000 ) to connect Citect to the Kingfisher RTU via TCP/IP. After Citect has finished starting up and reports all all I/O devices as "ONLINE", I then disconnect and re-connect the ethernet cable. Citect then fails to bring the all I/O devices online again. 

The driver code has been modified so that if the Kingfisher RTU does not respond after the TimeOuts and Retries, the communication channel is considered offline. This will put all I/O devices defined for that channel to be also considered offline and will be restarted.