Applies To: |
|
Summary: |
I have had a look through the documentation that comes with the ABRSLINX driver and still cannot get communications. The address field is confusing, what is the correct address? |
Solution: |
Data highway plus addressing is octal
whereas Citect addressing is decimal. I.e. 77o=63d.
You have a setup that is not documented. E.g. The Controllogix processor setup in "PLC5 emulation mode". If the processor is in slot 0 of the rack then the correct address is AB:ASA,1.0 An easy way to determine this is to set-up a DDE/OPC topic in RSLinx, select the advanced communication tab and have a look at the address as chosen by RSLinx. Another example. I have an SLC 5/04 connected to my PC via an older KF2 module. I can see it in RSLinx. Citect has a DH+ address of 0o77 and the KF2 module has a DH+ address of 0o62. The SLC has a DH+ address of 0o02. RSLinx is using the RS232-DF1 driver. Citect does not have a driver that will connect via the KF2 module, but obviously RSLinx does as it can see the device. As Citect has a driver that communicates to RSLinx, then it would make sense that a communication solution is possible. If you read the documentation that comes with the driver than it would make sense that the address would be AB:LOCAL/L:50,2. However, this does not work. If you have a look in the DDE/OPC topic in RSLinx then you will see that the 62 has no mention. (NB it 62o=50d) If you then change the address to AB:LOCAL,2 you will find that it communicates. This is the most reliable method of determining addresses to be used with the ABRSLINX driver. |
Keywords: |
Related Links
Attachments