Applies To:
  • CitectSCADA 4.xx, 5.xx

When the Wizard button is used with a graphic object, and a cicode function with a very large argument list exists, then the Citect Editor can crash. 

The fix prevents the Citect Editor from crashing. Cicode functions with very long argument lists, will not be selectable through the function wizard. A cicode function will be selectable through the wizard if the total length of the function name plus parameters is less than 254 characters. If the length exceeds this, the error message "Text Too Big" will appear in the list of functions returned by the wizard.

CIT has confirmed this to be a problem in Citect for Windows versions 5.00, 5.10 and 5.20.  This problem has been fixed in version Citect for Windows versions 5.21.