A new Citect.ini parameter has been added
for the MODNET driver. The parameter is called
SetNRDDisconnectExceptionErrorAsOffline. By default its value is 0,
indicating the exception error 0x1d will be treated as a general
error. If required to make this exception error take the unit
offline, set the parameter value to 1. Later versions of firmware
for NR&D Modnet gateways return instead the standard Modbus
exception error 0xb, which will result in the unit going offline
under this error condition.
CIT has confirmed this to be a problem in the MODNET driver.
This problem has been fixed in version 2.04.01.000 of the
driver.
|