Applies To: |
|
Summary: |
I have a modbus-compatible power monitor but have a problem reading data from this unit using modbus driver. |
Solution: |
To retrieve values/data from the device, a
dip switch on the device needs to be set and some Citect.INI
[MODBUS]parameters need to be added.
Dip Switch settings, by default, all dip switches are switched to "OFF". This gives the following setup; 8 Bits Note: To activate IEEE data format, dip switch 4 must be set to "ON". The following [MODBUS] parameters must exist in the Citect.INI file; [MODBUS] All data types are Citect REAL. Except 40001, 40002, 40003, 30021, 20025 which are LONG Citect data type. |
Keywords: |
Related Links
Attachments