Applies To: |
|
Summary: |
The memory used by Tag Import/Export is not fully released. This will cause Windows to run out of System Virtual Memory when a large number of tags are being imported or exported. |
Solution: |
CIT has confirmed this to be a problem in
Citect for Windows versions 5.20 to 5.31. This problem has been
fixed in version 5.41.
Workaround: When low virtual memory occurs, shutdown Citect Explorer and restart it again. The Windows Operating System will recover the memory leaked by Tag Import/Export. |
Keywords: |
Related Links
Attachments