Applies To:
  • CitectSCADA 5.41

Summary:
The maximum number of 64 Included Projects is not sufficient for warehouse type applications. 

Solution:
The maximum number of Included Projects allowed has been increased from 64 to 240 (including the Include project) in version 5.41 and later. In order to have 240 included projects you must set the parameter [CtEdit]DbFiles to its maximum value, 254. If the Citect compiler emits "out of handle" error, it means that the compiler has hit some internal limit and this is a known issue. Suggested solution is to reduce the number of include projects or contact Citect Customer Support. 