Applies To:
  • CitectSCADA 5.40, 5.40 Service Pack A, 5.40 Service Pack B

If a trend page has several pens set to trend tags, and these pens' numbers are not continuous, the trend printing will miss the x axis.

For example, on a standard "singletrend" page, the problem occurs if you set the pen 1, 6, 8 referring to trend tags.


CIT has confirmed this to be a problem in Citect for Windows versions 5.40 to 5.40 Service Pack B Rev 1. This problem has been fixed in version 5.41.