Applies To:
  • CitectSCADA 5.31, 5.40

Summary:
The maximum span of data that can be successfully retrieved by a TrnExport function has been greatly reduced. The times and received sample values will be incorrect if the period times the length of a TrnExport function request is greater than approximately 25 days.  

Solution:
CIT has confirmed this to be a problem in Citect for Windows versions 5.31 to 5.40. This problem has been fixed in version 5.41. 

Keywords:
 

Attachments