Applies To: |
|
Summary: |
A corrupt master trend file (a trend data
file with an .hst extension) may cause Citect to display the
following error message and then shutdown.
Assertion Failed! Program: D:\citect\bin\citect32.exe File: c:\citect\v531r0\source\cit\commonlib... Line:774 Expression ncount >=0 |
Solution: |
Deleting the master trend file will allow
Citect to start up normally.
CIT has confirmed this to be a problem in Citect for Windows versions 5.31 to 5.40 Service Pack B. This problem has been fixed in version 5.41. |