Applies To: |
|
Summary: |
Citect Help says that a maximum number of
16 characters is allowed for Group Names.
However, in both CitectSCADA Versions 5.40 SPK C and 5.41, when a Group name of 16 characters is defined and then inserted into the "viewable areas" section in the "System/User" form in the Citect project editor; a compile error would come up which says "group not found." |
Solution: |
The temporary work around is to use only
15 characters when using the group name in the "Viewable Area"
section.
Citect Pty Ltd is researching the cause of this problem. |
Keywords: |
Related Links
Attachments