Applies To:
  • CitectSCADA 5.40, 5.40 Service Pack A, 5.40 Service Pack B, 5.41

Citect Help says that a maximum number of 16 characters is allowed for Group Names.

However, in both CitectSCADA Versions 5.40 SPK C and 5.41, when a Group name of 16 characters is defined and then inserted into the "viewable areas" section in the "System/User" form in the Citect project editor; a compile error would come up which says "group not found."


The temporary work around is to use only 15 characters when using the group name in the "Viewable Area" section.

Citect Pty Ltd is researching the cause of this problem.