If you write to the properties of a number
of alarms consecutively, eg. to acknowledge alarm by setting
alarmtagname.ack = 1, not all of them will succeed.
The original workaround provided in KB Q3073 may require a long time sleeping in each call, which is sometimes not acceptable. |
Solution: |
An interim solution to workaround this
problem may be obtained by setting the following Citect INI
parameter:
[IOServer] Citect has confirmed this to be a problem in Citect for Windows versions 5.20 to 5.40 and CitectHMI/SCADA version 5.41. This problem has been fixed in version 5.41 Service Pack A. |