Applies To:
  • CitectSCADA 5.xx to 5.40, 5.41
  • CitectHMI 5.41

Summary:
If the current project in Citect Explorer has a "Citect.ini" file in its project directory and the /i parameter is not used to explicitly specify which "Citect.ini" file is being used, then "View | Configuration" will default to the "Citect.ini" file in the project directory and not the one in the Windows System Directory as it should. 

Solution:
Citect has confirmed this to be a problem in Citect for Windows versions up to 5.40 and CitectHMI/SCADA Version 5.41. This problem has been fixed in version 5.41 Service Pack A.

Keywords:
 

Attachments