Applies To:
  • CitectSCADA 5.xx, 5.41 
  • CitectHMI 5.41

Summary:
When Sorting is enabled and [Alarm]SummaryMode = 1 or 3 CitectSCADA will crash when the Alarm Summary List grows to the size of [Alarm]SummaryLength. 

Solution:
Citect has confirmed this to be a problem in Citect for Windows versions up to 5.40 and CitectHMI/SCADA version 5.41. This problem has been fixed in version 5.41 Spk A. There is also a workaround, which is to ensure that [Alarm]SummaryMode is set to 0 or 2. 

Keywords:
 

Attachments