Applies To: |
|
Summary: |
CitectHMI/SCADA v5.41r0 CCM Driver DBFs
files only have 1 row
This causes the compile error "Bad IO Device variable" for I/O Devices configured to use the CCM protocol. Files affected - DL205.dbf DL305.dbf GE_6.dbf GE_9030.dbf GE_9070.dbf TI_325.dbf TI_405.dbf TI_SG8.dbf |
Solution: |
The file GE_9030M.dbf has the correct
entries in it for the GE9030 copying the details from this file to
the GE_9030.dbf (or renaming the file) will correct the problem in
most cases.
Installing the driver, from the website, will also rectify the problem. |