Applies To:
  • CitectSCADA 5.41
  • CitectHMI 5.41

Summary:
CitectHMI/SCADA v5.41r0 CCM Driver DBFs files only have 1 row

This causes the compile error "Bad IO Device variable" for I/O Devices configured to use the CCM protocol.

Files affected -

DL205.dbf

DL305.dbf

GE_6.dbf

GE_9030.dbf

GE_9070.dbf

TI_325.dbf

TI_405.dbf

TI_SG8.dbf

 

Solution:
The file GE_9030M.dbf has the correct entries in it for the GE9030 copying the details from this file to the GE_9030.dbf (or renaming the file) will correct the problem in most cases.

Installing the driver, from the website, will also rectify the problem.

 