Applies To:
  • CitectSCADA 5.40, 5.40 Service Pack A, 5.40 Service Pack B, 5.41
  • CitectHMI 5.40, 5.40 Service Pack A, 5.40 Service Pack B, 5.41

Summary:
If using the cicode function _ObjectCallMethod to call a specific method for an ActiveX object, CitectHMI/SCADA may crash randomly. 

Solution:
Citect has confirmed this to be a problem in CitectHMI/SCADA versions 5.40 to 5.41SpkA. This problem has been fixed in version 5.41SpkB. 

Keywords:
 