Applies To:
  • CitectSCADA 5.xx
  • CitectHMI 5.xx

Summary:
The latest MicrexSX driver V1.01.03.000 cannot read STRING data type from addresses such as MW3String.400. Driver error 0x100 is generated if attempting to display such an address on a page. 

Solution:
The MicrexSx driver cannot read STRING data types. Citect confirmed this was a problem and had been rectified in version V1.01.04. 

Keywords:
 

Attachments