Applies To:
  • CitectSCADA 5.40, 5.41
  • CitectHMI 5.40, 5.41

Summary:
The ABTCP driver (v2.04.05.000) in standard version 5.41 does not support writing to REALs properly. The wrong value gets written to the PLC. 

Solution:
A newer ABTCP driver (v2.04.06.000) exists that fixes this problem. This can be obtained from MyCitect downloads and will be updated in a later release of CitectSCADA. 

Keywords:
 

Attachments