Applies To: |
|
Summary: |
When using CompactLogix PLC with the ABLOGIX driver, communications is slow and produces many errors. |
Solution: |
The ABLOGIX driver is primarily designed
for the ControlLogix PLC which has a higher performance than the
CompactLogix PLC.
It has been found that communications speed is much improved and errors eliminated by: * reducing the citect.ini parameter MaxPending from 15 to 5. [ABLOGIX] * Increasing the 'system overhead timeslice' to 50% (on the 'advanced' tab of the controller properties in the RSLogix5000 software) |
Keywords: |
Related Links
Attachments